Specifications
REV-2250
REV-3000
REV-4500
REV-6000
Airflow Information
Nom. Supply Airflow (cfm)
2,250
3,000
4,500
6,000
Max Supply Airflow (cfm)
3,600
4,800
7,200
9,600
Max Outdoor Airflow (cfm)
2,250
3,000
4,500
6,000
Cooling-Dehumidification Performance
(
note
)
Maximum Supply Flow with 30% Outdoor Air
(
note
)
Range of Sensible Cooling Output (btu/hr)
50,000-82,000
67,000-110,000
100,000-165,000
133,000-220,000
Range of Latent Cooling Output (btu/hr)
80,000-56,000
107,000-75,000
160,000-112,000
213,000-150,000
Range of SHR
(sensible heat ratio)
.38 - .60
.38 - .60
.38 - .60
.38 - .60
Supply Humidity
(
note
)
(grains/dew point °F)
51/49
51/49
51/49
51/49
Nominal Supply Flow with 30% Outdoor Air
(
note
)
Range of Sensible Cooling Output (btu/hr)
34,000-70,000
46,000-95,000
68,000-140,000
90,000-185,000
Range of Latent Cooling Output (btu/hr)
73,000-58,000
97,000-77,000
145,000-115,000
195,000-155,000
Range of SHR
(sensible heat ratio)
.32 - .55
.32 - .55
.32 - .55
.32 - .55
Supply Humidity
(
note
)
(grains/dew point °F)
36/39.5
36/39.5
36/39.5
36/39.5
100% Outdoor Air
(
note
)
Range of Sensible Cooling Output (btu/hr)
34,000-76,000
46,000-101,000
68,000-151,000
91,000-201,000
Range of Latent Cooling Output (btu/hr)
110,000-75,000
147,000-100,000
220,000-150,000
293,000-200,000
Range of SHR
(sensible heat ratio)
.24 - .50
.24 - .50
.24 - .50
.24 - .50
Supply Humidity
(
note
)
(grains/dew point °F)
48/47
48/47
48/47
48/47
Max Heating Performance: Indirect Gas Option
(
note
)
Max Heating Capacity (btu/hr)
175,000
227,000
280,000
280,000
Temperature Rise
(nom. supply airflow, °F)
72
70
58
43
Temperature Rise
(max supply airflow, °F)
45
44
36
27
Max Heating Performance: Heat Pump Option
(
note
)
Max Heating Capacity (btu/hr)
165,625
231,875
331,250
397,500
Temperature Rise
(nom. supply airflow, °F)
68
72
68
61
Temperature Rise
(max supply airflow, °F)
43
45
43
38
Compressor Information
Maximum (tons)
12.5
17.5
25
30
Minimum (tons)
10
15
20
25
Refrigerant Used
R-22
R-22
R-22
R-22
Capacity Control
Variable speed compressor
Regeneration Information
(
note
)
Max Regeneration Airflow (cfm)
660
880
1,320
1,760
Max Regeneration Energy (btu/hr)
89,100
118,800
178,200
237,600
Fuel Utilized
Direct fired natural gas
Max Regeneration Temperature (°F)
210
210
210
210
System Information
(
note
)
Dimensions (L x W x H)
171” x 65” x 48"
186” x 67” x 57"
197” x 80” x 71"
213” x 90” x 74”
Weight (pounds)
2,000
2,800
3,300
4,500
Voltage Options
208/230/460/3Ø